No.
Type
Open
High Temp. 2
22
Shutdown
Low Pressure 2
23
Shutdown
Low Coolant Level
24
Shutdown
25
Maintenance Due
Over Power Shutdown
26
Alarm
Digital Input Port Alarm
27
Shutdown
28
ECU Alarm Shutdown
ECU Fail to
29
Communication
NOTE: ECU warning and shutdown alarms illustration: if there are detailed alarms displayed, check the engine
according to the information; otherwise refer to the engine manual to obtain information according to SPN alarm code.
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
sensor port, is open circuit, and the open circuit action in
parameter configuration is selected "shutdown", it will send stop
alarm signals and the corresponding alarm information will be
displayed on LCD.
When the sample value adopted by the programmable sensor
(sensor type: temperature sensor), is higher than the pre-set
value, it will send stop alarm signals and the corresponding
alarm information will be displayed on LCD.
When the sample value adopted by the programmable sensor
(sensor type: pressure sensor), is lower than the pre-set value, it
will send stop alarm signals and the corresponding alarm
information will be displayed on LCD.
When the sample value adopted by the programmable sensor
(sensor type: liquid level sensor), is lower than the pre-set value,
it will send stop alarm signals and the corresponding alarm
information will be displayed on LCD.
When genset operation time exceeds the users-set maintenance
time and the maintenance action is set "shutdown", it will send
stop alarm signals and the corresponding alarm information will
be displayed on LCD.
When the controller detects the power value (power is positive)
is higher than the set limit value and the over power action type
is set "shutdown", it will send stop alarm signals and the
corresponding alarm information will be displayed on LCD.
When the controller detects external shutdown alarm signals are
active, it will send stop alarm signals and the corresponding
alarm information will be displayed on LCD.
When the controller receives the stop alarm signals by J1939, it
will send stop alarm signals.
When the controller does not receive data by J1939 when it
starts the engine, it will send stop alarm signals for
communication failure.