Smartgen HGM4100LT User Manual page 23

Genset controller
Table of Contents

Advertisement

No
Items
45
Digital Input 2
Digital
Input
46
Active
Digital
Input
47
Delay
48
Digital Input 3
Digital
Input
49
Active
Digital
Input
50
Delay
51
Digital Input 4
Digital
Input
52
Active
Digital
Input
53
Delay
54
Digital Input 5
Digital
Input
55
Active
Digital
Input
56
Delay
57
Power On Mode
58
Module Address
59
Password Setting
Crank
60
Disconnection
Conditions
Engine Speed at
61
successful start
Generator Freq. at
62
successful start
Oil
Pressure
63
successful start
High Temperature
64
Inhibit
Low Oil Pressure
65
Inhibit
Low
Fuel
Level
66
Inhibit
Flexible
Sensor
67
Inhibit
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
Range
Default
(0-31)
2
2
(0-1)
0
2
(0-20.0)s
2.0
(0-31)
10
3
(0-1)
0
3
(0-20.0)s
2.0
(0-31)
11
4
(0-1)
0
4
(0-20.0)s
2.0
(0-31)
12
5
(0-1)
0
5
(0-20.0)s
2.0
(0-2)
0
(1-254)
1
(0-9999)
0318
(0-6)
2
(0-6000)r/min 360
(10.0-30.0)Hz 14.0
at
(0-400)kPa
200
(0-1)
0
(0-1)
0
(0-1)
1
(0-1)
1
2019-01-28
Description
Factory default: Low Oil Pressure Alarm input.
For details please see Table 9.
Factory default: active when it is closed;
Factory default: Remote Start input; for details
please see Table 9.
Factory default: Active when it is closed;
Factory default: Low Fuel Level Warning input;
For details please see Table 9.
Factory default: Active when it is closed;
Factory default: Low Coolant Level Warning
input. For details please see Table 9.
Factory default: Active when it is closed;
0: Stop Mode 1: Manual Mode 2: Auto Mode
Communication address of controller;
For details please see
Conditions for successful start of starter; they
are Generating, Speed and Oil pressure. Their
aim is to make the motor disconnect with the
engine as soon as possible.
When engine speed is higher than the set
value, the starter will be disconnected.
When generator frequency is higher than the
set value, the starter will be disconnected.
When generator oil pressure is higher than the
set value, the starter will be disconnected.
Factory default: when high temperature occurs,
shutdown alarm is initiated. For function details
please see
NOTE 2.
Factory default: when low oil pressure occurs,
shutdown alarm is initiated. For function details
please see
NOTE 3.
Factory default: when low fuel level occurs,
shutdown alarm is initiated. For function details
please see
NOTE 4.
Factory default: when configuration sensor
value is higher/lower than the set value
(particular case depends on the sensor type),
Version1.0
NOTE 6.
Page 23 of 48