fuel level alarm input signal is active, the controller shall only send low fuel level warning signal and not
shutdown the genset;
4)
Multiplex input port can choose any one of digital input type and sensor and it is active after configuration. e.g.
multiplex input 4: when it is configured to digital input, the related configuration options of digital input 4 are
active; if it is configured to level sensor, then the related level sensor options are active;
5)
When parameter configuration is done via PC software, there is no need to input password if default password
(0318) isn't changed; otherwise, if default password has been changed or it is the first time to set parameters
via PC, password is needed to write on the password interface;
6)
After the correct password is entered and before the LCD backlight goes dark, if users try to enter password
input interface, they can input the parameter No. directly and enter the setting interface;
7)
On the flywheel teeth configuration interface, when the generating frequency is over 20 Hz, press the Start key,
and it can calculate the teeth number automatically. Press Confirm key and the teeth number can be changed.
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL