Smartgen HGM4100LT User Manual page 30

Genset controller
Table of Contents

Advertisement

No
Items
10
Remote Start
11
Fuel Level Warning
12
Coolant Level Warning
13
Fuel Level Shutdown
14
Coolant Level Shutdown
15
Inhibit Start Auto
16
Remote Control Mode
17
Charge Alt Fail Input
18
Panel Lock
19
Manual/Auto Switch
20
Alarm Mute
21
Idle Input
22
Raise Speed Pulse
23
Drop Speed Pulse
24
Idle Pulse Input
25
60Hz Select
26
External Shutdown Alarm
27
Reserved
28
Reserved
29
Reserved
30
Reserved
31
Reserved
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
When this input is active in auto mode, genset starts automatically
and loads after running. Otherwise, genset will stop automatically
if it is inactive.
Connected to digital input port of sensor, if this input is active,
controller will send warning alarm signal.
Connected to digital input port of sensor, if this input is active,
controller will send shutdown alarm signal.
In Auto mode, if this input is active, whether remote start input is
active or not, the controller will not give a start command to the
generator. If generator is normal running, stop command won't be
executed. When this input is deactivated, genset will automatically
start or stop according to remote start input (active or inactive).
When the input is active, keys on the panel are locked except for
and remote mode will be displayed on the LCD.
Remote control module pattern can be switched by the key on the
panel.
Connected to charge alt failure output port.
When input is active, all keys expect the
th
inactive. The 4
row of the LCD displays the icon
When input is active, it enters auto mode automatically, panel
buttons are unavailable; When input is inactive, it enters manual
mode automatically, control buttons on the panel are recovered.
When the input is active, it prohibits "Audible Alarm" output.
Idling speed control outputs when it is active.
Used for ECU genset with CANBUS interface.
Used for ECU genset with CANBUS interface.
Used for ECU genset with CANBUS interface.
Used for ECU genset with CANBUS interface. When it is active,
the frequency is 60Hz.
Genset will alarm and shutdown immediately if the signal is active.
2019-01-28
Description
Version1.0
buttons are
.
Page 30 of 48

Hide quick links:

Advertisement

Table of Contents
loading