No
Items
68
Voltage Input
Temp.
Sensor
69
Curve
Pressure
Sensor
70
Curve
Multiplex
Input
71
Liquid
Level
Sensor
Level
Sensor
72
Curve
Multiplex
Input
73
Programmable
Sensor
Flexible
Sensor
74
Curve
75
Generator Poles
Temp. Sensor Open
76
Circuit Action
Oil Pressure Sensor
77
Open Circuit Action
Level Sensor Open
78
Circuit Action
Flexible
Sensor
79
Open Circuit Action
80
Cooler On Set Value (0-255)℃
Cooler
Off
Set
81
Value
Low
Fuel
Level
82
Warning
Gen
Over
83
Warning
Gen
Under
84
Warning
HGM4100LT Genset Controller
Range
Default
(0-3)
0
(0-12)
8
(0-12)
8
(0-1)
0
(0-7)
3
(0-3)
0
(0-9)
8
(0-9)
8
(0-5)
3
(2-64)
4
(0-2)
1
(0-2)
1
(0-2)
1
(0-2)
1
60
40
(0-255)℃
(0-100)%
20
Volt
(30-620)V
253
Volt
(30-620)V
193
2019-01-28
HGM4100LT GENSET CONTROLLER USER MANUAL
warning alarm is initiated. For details please
see 64,65,66 Setting Items.
0: 3P4W; 1: 2P3W; 2: 1P2W; 3: 3P3W
SGX; For details please see Table 10.
SGX; For details please see Table 10.
0: Aux. Input 4 Configuration
1: Liquid Level Sensor
For details please see
SGD; For details please see Table 10.
0: Aux. Input 5 Configuration
1: Temperature Sensor
2: Pressure Sensor
3: Liquid Level Sensor
For details please see
SGX;
SGX;
SGD;
Number of generator magnetic poles; it can be
used to calculate the engine speed when speed
sensor is not installed.
0: Indication 1: Warning; 2: Shutdown
"Indication" means "+++" shall be displayed on
LCD at the position of corresponding sensor.
When air cooler is configured in a output port, it
controls the open and close.
When the liquid level of the external sensor falls
below the set value, "Low Fuel Level" delay is
initiated. (this only concerns fuel level sensor
and does not concern low fuel level warning
signal via configurable input port.)
When generator voltage exceeds pre-set value,
gen over voltage warning alarm will be sent.
(No detection for over volt signal if the value is
set 620V.)
When the sample voltage is below pre-set
value, gen under voltage warning alarm will be
sent. (No detection for under volt signal if the
value is set 30V.)
Version1.0
Description
NOTE 5.
NOTE 5.
Page 24 of 48