Cummins Gcs-Modbus; Cummins Qsm11; Cummins Qsz13 - Smartgen HGM4100LT User Manual

Genset controller
Table of Contents

Advertisement

13.5 CUMMINS GCS-MODBUS

It is suitable for GCS engine control module. Read engine information by using RS485-MODBUS.
Engine types are QSX15, QST30, QSK23 / 45/60/78 and so on.
Terminals of controller
Programmable output1
Start relay output
Terminals of controller
RS485 GND
RS485+
RS485-
Engine type: Cummins QSK-MODBUS, Cummins QST-MODBUS, Cummins QSX-MODBUS.

13.6 CUMMINS QSM11

Terminals of controller
Programmable output1
Start relay output
CAN_SCR
CAN(H)
CAN(L)
Engine type: common J1939.

13.7 CUMMINS QSZ13

HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
Table 21 D-SUB Connector 06
D-SUB connector 06
5&8
-
Table 22 D-SUB Connector 06
D-SUB connector 06
20
21
18
Table 23 Engine OEM Connector
engine OEM connector
38
-
-
46
37
2019-01-28
Remark
Set configurable output 1 as "Fuel Relay
Output".; Outside expand relay; when fuel
outputs, make port 06 and 08 of the
connector 06 be connected;
Connected to starter coil directly;
Remark
CAN
communication
(connected to ECU terminal only);
Using impedance 120Ω connecting line;
Using impedance 120Ω connecting line;
Remark
Set configurable output 1 as "Fuel Relay
Output";
Connected with starter coil directly;
CAN
communication
(connected with controller's this terminal
only);
Using impedance 120Ω connecting line;
Using impedance 120Ω connecting line;
Version1.0
shielding
line
shielding
line
Page 42 of 48