SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

7.1

CONTENTS AND SCOPES OF PARAMETERS

No
Items
1
Start Delay
2
Stop Delay
3
Start Attempts
4
Preheat Delay
5
Cranking Time
6
Crank Rest Time
7
Safety On Delay
8
Start Idle Time
9
Warming Up Time
10
Cooling Time
11
Stop Idle Time
ETS Solenoid Hold (0-120)s
12
13
Fail to Stop Delay
14
Switch Close Time
15
Flywheel Teeth
HGM4100LT Genset Controller
Cable
Size
monitoring
1.5mm
1.5mm
Table 7 Contents and Scopes of Parameter Settings
Range
Default
(0-3600)s
1
(0-3600)s
1
(1-10)times
3
(0-300)s
0
(3-60)s
8
(3-60)s
10
(1-60)s
10
(0-3600)s
0
(0-3600)s
10
(3-3600)s
10
(0-3600)s
0
20
(0-120)s
5
(0-10)s
5.0
(10.0-300.0)
118.0
2019-01-28
HGM4100LT GENSET CONTROLLER USER MANUAL
Externally connected to CT secondary coil (5A
2
rated);
2
Reference to Installation Instruction
From time when remote start signal is active to
the time when the genset starts;
From time when remote start signal is reactive
to time when the genset stops;
The max. crank attempts for start failure; when
it reaches the crank times, the controller shall
send start failure signal.
Power-on time of heater plug before starter is
powered up;
Power-on time of starter every time;
The waiting time before the second power on
when engine fails to start;
During this period, low oil pressure, high
temperature, under speed, under frequency,
under voltage, charge alt failure alarms are all
inactive.
Running time at idling speed when genset
starts;
Warming up time before breaker close and after
high speed running;
Radiating time before genset stop, after it
unloads.
Idle running time when genset stop.
Power-on time for stop coil after genset
unloads;
Time from end of idling speed delay to complete
stop when ETS output time is set "0"; Time from
end of ETS delay to complete stop when ETS
output time is not "0";
Width of generator close pulse; Continuous
output when it is 0;
Flywheel teeth of engine; which is used for
judging starter disconnection conditions and
Version1.0
Remarks