Output percentage with loading
Overvoltage, undervoltage, overfrequency, underfrequency, overcurrent, overpower
functions for generating;
Precisely collecting all kinds of parameters for the generator:
Temp.
Oil Pressure
Fuel Level
Speed
Voltage of Battery
Voltage of Charger
Hour count accumulation
Start times accumulation
Control and protection function: automatic start/stop of the diesel genset, ATS (Auto
Transfer Switch) control and perfect fault indication and protection functions;
ETS (energize to stop), idling speed control, pre-heating control and speed rise/drop
control functions, which are all relay outputs;
Parameter setting function: it allows users to change and set parameters and
meanwhile they shall be stored in the internal FLASH. They shall not be lost even in case of
power outage; All of them can be adjusted from the front panel of the controller and also can be
modified on PC via USB or RS485 port;
Two multiplex input port 4 and 5; Input port 4 can be configured as switch input port or
fuel level sensor; input port 5 can be set as switch input port or programmable sensor. It can be
flexibly applied on different occasions.
Multiple temperature, pressure, oil level sensors can be used directly and their
parameters can be self-defined;
One programmable sensor; it can be configured as temperature, pressure or liquid
level sensor, which achieves the detection for double temperature, double pressure or double
liquid level;
Optional crank disconnection conditions (speed sensor, oil pressure, generating);
Emergency start function;
Automatic recognition function for flywheel tooth number;
Wide power supply range (8~35)VDC, which is suitable for different starting battery
voltage environment;
All parameters apply digital adjustment, getting rid of conventional analog modulation
of normal potentiometer, improving the reliability and stability of the whole device;
Maintenance function; maintenance types can choose date or running time,
maintenance actions can be configurable (reactive, warning, or alarm shutdown);
Event log, real-time clock, and scheduled start & stop function (start once each
day/week/month and loading or not can be set); Maximum event logs are 99 items;
Rubber seal designed between the shell and the screen with protection level IP65;
Metal fixing clips are used to fix the controller;
Modular structure design, anti-flaming ABS plastic enclosure, pluggable connection
terminals and embedded installation way with compact structure and easy mounting.
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
%
° C/° F
kPa/psi/bar all be displayed
%(unit)
Fuel Quantity Left L(unit)
r/min (RPM)
V (unit)
V (unit)
2019-01-28
Version1.0
Page 6 of 48