Smartgen HGM4100LT User Manual page 22

Genset controller
Table of Contents

Advertisement

No
Items
Flexible
Sensor
26
Values
Loss
of
Speed
27
Signal Delay
Voltage Difference
28
of
Charge
Failure
Battery
Over
29
Voltage
Battery
Under
30
Voltage
31
CT Ratio
32
Full Load Rating
Over
Current
33
Percentage
Over
Current
34
Delay
35
Fuel Pump On
36
Fuel Pump Off
37
Relay Output 1
38
Relay Output 2
39
Relay Output 3
40
Relay Output 4
41
Relay Output 5
42
Digital Input 1
Digital
Input
43
Active
Digital
Input
44
Delay
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
Range
Default
(80-140)º C
(0-400)kPa
98
(0-100)%
(0-20.0)s
5.0
(0-30)V
6.0
Alt
(12-40)V
33.0
(4-30)V
8.0
(5-6000)/5
500
(5-6000)A
500
(50-130)%
120
(0-3600)s
30
(0-100)%
25
(0-100)%
80
(0-31)
6
(0-31)
2
(0-31)
3
(0-31)
5
(0-31)
14
(0-31)
1
1
(0-1)
0
1
(0-20.0)s
2.0
2019-01-28
Description
and not shutdown of the generator.
The values correspond to the function settings
of 23 (Temperature sensor), 24 (Oil pressure
sensor) and 25 (Level sensor) respectively.
Shutdown delay of loss of speed signal; If the
set value is 0, it is only warning and not
shutdown.
During the normal running process, when the
voltage difference between alternator D+(WL)
and B+ exceeds the set value and remains for
5s, It will initiate a "charge alt failure" shutdown
alarm signal.
When battery voltage has exceeds the set value
and remains for 20s, It will initiate a warning
alarm signal. It is only warning and not
shutdown.
When battery voltage goes under the set value
and remains for 20s, It will initiate a warning
alarm signal. It is only warning and not
shutdown.
The ratio of external CT;
Generator's rated current; it is used for over
current loading calculation.
When the load current has exceeded the set
value, "over current delay" is initiated.
When load current has exceeded the set value
and the "over current" delay has expired, over
current alarm is initiated. When the set value is
0, it is only warning and not shutdown.
When fuel level has fallen below the set value
for 10s, "Fuel Pump On" signal outputs;
When fuel level has exceeded the set value for
10s, "Fuel Pump Off" signal outputs;
Factory default: Reserved; For details please
see Table 8.
Factory default: ETS control; For details please
see Table 8.
Factory default: Idling speed control; For details
please see Table 8.
Factory default: Gen breaker close; For details
please see Table 8.
Factory default: Fuel relay output; For details
please see Table 8.
Factory default: High Temperature Alarm input;
For details please see Table 9.
Factory default: Active when it is closed;
Version1.0
Page 22 of 48