Conditions Of Crank Disconnection Selection - Smartgen HGM4100LT User Manual

Genset controller
Table of Contents

Advertisement

7.5

CONDITIONS OF CRANK DISCONNECTION SELECTION

No.
0
Speed
1
Gen frequency
2
Speed + Gen frequency
3
Speed +Oil pressure
4
Gen frequency + Oil pressure
5
Speed + Gen frequency + Oil pressure
6
Oil pressure
NOTES:
1)
There are 3 conditions to make starter separate with engine; speed, generator frequency and oil pressure. All can be
used separately. It is suggested that oil pressure shall be used together with speed and generator frequency. The
aim is to disconnect the starter motor as soon as possible.
2)
Speed stands for the real rotation speed detected by the speed sensor. Speed sensor is the magnetic equipment
which is installed in the starter for detecting flywheel teeth.
When speed is chosen, make sure that the number of flywheel teeth is the same as the set value, otherwise, "over
3)
speed shutdown" or "under speed shutdown" may be caused.
If genset is without speed sensor, please don't select corresponding items, otherwise, "start fail" or "loss speed
4)
signal" maybe caused.
If genset is without oil pressure sensor, please don't select corresponding items.
5)
6)
If generator frequency is not chosen in crank disconnection setting, the controller will not collect and display the
relative power quantity (can be used in water pump set); if speed is not chosen in crank disconnection setting, the
engine speed displayed is converted by generator frequency and generator poles.
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
Table 11 Crank Disconnection Condition Selection
2019-01-28
Set Contents
Version1.0
Page 32 of 48

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents