Wire Connection - WAGO 750-370 Manual

Modular i/o-system fieldbus coupler profinet io
Hide thumbs Also See for 750-370:
Table of Contents

Advertisement

32 •
The WAGO-I/O-SYSTEM 750
Mechanical Setup

2.6.9 Wire Connection

All components have CAGE CLAMP® connections.
The WAGO CAGE CLAMP® connection is appropriate for solid, stranded
and finely stranded conductors. Each clamping unit accommodates one
conductor.
Fig. 2-9: CAGE CLAMP® Connection
The operating tool is inserted into the opening above the connection. This
opens the CAGE CLAMP
the opening. After removing the operating tool, the conductor is safely
clamped.
More than one conductor per connection is not permissible. If several
conductors have to be made at one connection point, then they should be made
away from the connection point using WAGO Terminal Blocks. The terminal
blocks may be jumpered together and a single wire brought back to the I/O
module connection point.
Attention
If it is unavoidable to jointly connect 2 conductors, then a ferrule must be used
to join the wires together.
Ferrule:
Length
Nominal cross section
WAGO Product
®
. Subsequently the conductor can be inserted into
8 mm
2
1 mm
for 2 conductors with 0.5 mm
max.
216-103 or products with comparable properties
g0xxx08x
2
each
WAGO-I/O-SYSTEM 750
PROFINET IO

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents