WAGO 750-370 Manual page 233

Modular i/o-system fieldbus coupler profinet io
Hide thumbs Also See for 750-370:
Table of Contents

Advertisement

Parameter
Default value behavior of the
outputs
Process data format channel x
(x = 0.1)
Substitute output data channel x
(x = 0.1)
WAGO-I/O-SYSTEM 750
PROFINET IO
Configuration and Parameter Setting of the Modules
Value
according to the device settings*)
Outputs are set to 0
Outputs maintain the last valid value
Outputs take on their default value
according to the device settings*)
INTEL (LSB-MSB)
MOTOROLA (MSB-LSB)
*)
0x0000
– 0x7FFF
or
*)
0x0000
– 0xFFFF
*) Default settings
I/O Modules
Significance
In case the I/O controller does not supply valid
output data for the module or the group of modules
then
the set strategy on the side of the station
distributor applies (I/O device).
all outputs are immediately reset
all outputs maintain the last valid value
all outputs switch to their configured
substitute value
The process data will be transferred
transfer the settings of the I/O device.
Little Endian Format
Big Endian Format
If the switching of substitute values has been
selected as a fault strategy, the substitute output
data of the individual output channels can be
determined here.
• 233

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents