Standard Module Parameters

Certain characteristics of some I/O modules can be parameterized during the
configuration. At present, this only applies to the output modules whose
substitute value behavior can be set independent of the modules used.
Parameter
Substitute value
behavior
of the outputs
WAGO-I/O-SYSTEM 750
PROFINET IO
Setting
according to the device
settings*)
according to the
referenced module
2
settings*)
)
Output values are set
to 0
Outputs maintain the
last valid value
outputs take on their
default value
*) Presetting
2) Digital modules whose process data has been allocated
to their previous slots implicitly take over the default
value strategy of the module on the slot allocated.
PROFINET IO 750-370
I/O Device Configuration
Description
In case the I/O controller does not
supply valid output data for the
module or the group of modules then
the set strategy on the side of the
station substitute applies (I/O
device).
the set strategy on the side of the
referenced digital module by which
the output data has been reserved.
These settings apply to digital output
modules without process data. These
are characterized using a * behind
the item number.
all outputs are immediately reset
all outputs maintain the last valid
value
all outputs switch to their configured
substitute value