84 •
PROFINET IO 750-370
Process Image
3.1.5.2.5.4

PROFIsafe I/O Modules

The consumer status (IOPS) of the input or output information is exchanged
between the I/O controller and I/O device in both directions with PROFIsafe
I/O modules.
The following table shows a list of the number of bytes for the individual
modules that are allocated in the respective process image (PA) and the
telegrams (TLG) in the direction of transmission and reception (Tx, Rx).
Type
PROFIsafe
3.1.5.2.6

System Modules

3.1.5.2.6.1

Potential Supply Modules

The group of potential supply modules is divided into 2 types of modules:
Type of module
In case there is no diagnostics data prepared in the input image, potential
supply modules supply a provider status (IOPS) to the I/O controller. If the
input data is available in the input process image then the consumer status
(IOCS) is received from the I/O controller.
The following table shows a list of the number of bytes for the individual
modules that are allocated in the respective process image (PA) and the
telegrams (TLG) in the direction of transmission and reception (Tx, Rx).
Type
Module
Data length [Byte]
PA
TLG
E
A
Tx
5
5
7
Description
Supply module
2DIA
with 2 Bit diagnostics
Supply module
with 2 Bit diagnostics,
2DIA_PI
and additional diagnostics with
input image
Module
Data length / [Byte]
PA
E
A
2DIA
0
0
1
0
2DIA_PI
2
0
4
0
753-661/000-002
753-662/000-002
75x-667/000-002
4F-DE/DA
Data object
E
INST
Rx
7
U8[5]
1
750-6xx
...
Data type
TLG
E
A
Tx
Rx
1
0
-
-
2
1
UINT8
-
3
1
UINT16
-
5
1
UINT32
-
4F-DE
8F-DE
A
INST
U8[5]
1
Substitute I/O modules
750-610, 750-611
750-610, 750-611
750-6xx*
Data length / [Byte]
PA
TLG
E
A
Tx
Rx
0
0
1
1
WAGO-I/O-SYSTEM 750
PROFINET IO
...
Data type
E
A
-
-