96 •
PROFINET IO 750-370
Diagnostics
Article
number
750-661,
750-662,
750-667
Data
Fault type
format
BIT
0x18 / 24
OTHER
0x40 / 64
0x41 / 65
0x42 / 66
0x43 / 67
0x44 / 68
0x45 / 69
0x46 / 70
0x47 / 71
0x01 / 1
0x19 / 25
0x1B / 27
0x1C / 28
0x1E / 30
Significance
Fault PROFIsafe
There is an external fault on and input or
I/O module
output channel. The detailed cause of fault
can be determined using the record data set
of the module (see also documentation on
PROFIsafe I/O modules).
There is a module fault, e.g. program
sequence fault. The detailed cause of a fault
can be determined using the record data set
of the module (see also documention on
PROFIsafe I/O modules).
The F-device address set by the I/O module
Wrong
differs from the addresses set during
F-Host address
configuration.
Invalid
The F-device address has been configured
F-device address
with 0 or 65535.
Wrong
The F-Host address set during projection
F-Host address
differs.
Invalid
The F-Host address has been configured with
F-Host address
0 or 65535.
SIL class
One SIL class has been configured that is not
not supported
supported by the F-device.
Wrong
An F-CRC length unequal to 2 bytes has
F-CRC length
been configured.
Wrong
An F-parameter set version unequal to
version of the
PROFIsafe V2 has been configured.
F-parameter set.
Invalid CRC of the
The F-parameter set is inconsistant.
F-parameter set
Short curcuit
Safety shutdown
Short circuit after
VCC
Short circuit after
GND
Discrepancy time
exceeded
WAGO-I/O-SYSTEM 750
PROFINET IO