Parameter Setting; Station Parameters - WAGO 750-370 Manual

Modular i/o-system fieldbus coupler profinet io
Hide thumbs Also See for 750-370:
Table of Contents

Advertisement

Module
DIA_0
3.1.3.3

Parameter Setting

3.1.3.3.1

Station Parameters

The parameters of the station substitute are used to set the overall settings of
the PROFINET IO node. Some of the settings are used in the modules as
default settings and can be optionally overwritten within the module
configuration.
Parameter
Restart the internal
bus after a fault
Internal Data Bus
Extension
Message external
module / channel
fault
Process value
display
WAGO-I/O-SYSTEM 750
PROFINET IO
Description
The 2 bit diagnostics information are not
available in the input process image of the
I/O controller.
Setting
POWER ON RESET*)
AUTORESET
EEPROM setting*)
not used
used
locked
released*)
INTEL (LSB-MSB)
MOTOROLA (MSB-
LSB)*)
PROFINET IO 750-370
I/O Device Configuration
Exemplary name
750-610 P- Supply, DIA
Description
Restart of the internal data bus
following a fault, such as, for
example, no end module following:
after an interruption of the buscoupler
supply
immediately after overcoming the
internal bus fault
Use of the internal data bus extension.
Based upon the settings made in
EEPROM that are made using the
"WAGO Extension Settings" tool.
is excluded
is possible
The external diagnostics information
of all diagnostics capable I/O modules
are:
not transferred to the PROFINET
I/O Controller
transferred to the PROFINET
I/O Controller
Word or double word orientated
process data are transfered to the
PROFINET I/O Controller in:
"Little Endian" format
"Big Endian" format
• 65

Hide quick links:

Advertisement

Table of Contents
loading