122 •
PROFINET IO 750-370
LED Indication
10
Buffer power failure real time
clock (RTC)
11
Fault during read access to the
real time clock (RTC)
12
Fault during write access to the
real time clock (RTC)
13
Clock interrupt fault.
14
Maximum number of gateway
modules or mailbox modules
exceeded.
Set the clock and hold up the
power supply of the buscoupler for
at least 15 minutes in order to
charge the Goldcap.
Set the clock and hold up the
power supply of the buscoupler for
at least 15 minutes in order to
charge the Goldcap.
Set the clock and hold up the
power supply of the buscoupler for
at least 15 minutes in order to
charge the Goldcap.
Set the clock and hold up the
power supply of the buscoupler for
at least 15 minutes in order to
charge the Goldcap.
Reduce the number of
correspondent modules to a valid
number.