Configuration and Parameter Setting of the Modules
Parameter
Substitute value behavior of the
outputs
Substitute output status channel
x
(x = 0 ... 7)
Value
according to the device settings*)
Outputs are set to 0
Outputs maintain the last valid
value
Outputs take on their substitute
value
*)
0
1
*) Default settings
Significance
In case the I/O controller does not supply valid
output data for the module or the group of modules
then
•
the set strategy on the side of the station
substitute applies (I/O device).
•
all outputs are immediately reset
•
all outputs maintain the last valid value
•
all outputs switch to their configured substitute
value
When configuring the substitute value behavior on
the side of the I/O module, these values are
transmitted to the binary signal channel with invalid
output states of the I/O controller.