Module
DI_DIA_0
DO_DIA_32
DO_DIA_16
Description
Configuration module for filling input
information previously reserved by
modules DI_32, DI_DIA_32
DI_16, DI_DIA_16, DI _8 or DI _8. Care
must be taken that the number of previously
reserved input bits is sufficient to receive
the existing input and diagnostic
information of the configured I/O module
(represented in brackets with a negative
sign).
Configuration module for 32 digital input
and outputs, 4 bytes are reserved in the
output and output process image of the I/O
controller. The bit information in the first
byte of the output area is allocated to the
output data of the configured I/O module
according to the number of existing signal
channels. The bit information in the first
byte of the input area is allocated to the raw
diagnostics data of the individual signal
channels. Remaining bit locations of the
reserved input and output area (indicated in
brackets with a positive sign) can be
allocated to the signal conditions of the
following digital I/O modules having the
same type of signal. This is done by
configuring the Dx0 or Dx_DIA_0 modules
of the relevant I/O modules.
Configuration module for 16 digital input
and outputs, 2 bytes are reserved in the
output and output process image of the I/O
controller. The bit information in the first
byte of the output area is allocated to the
output data of the configured I/O module
according to the number of existing signal
channels. The bit information in the first
byte of the input area is allocated to the raw
diagnostics data of the individual signal
channels. Remaining bit locations of the
reserved input and output area (indicated in
brackets with a positive sign) can be
allocated to the signal conditions of the
following digital I/O modules having the
same type of signal. This is done by
configuring the Dx0 or Dx_DIA_0 modules
of the relevant I/O modules.
Name example
75x-425* 2DE(-4 BIT E),
DIA in E-PA
75x-507 2DA(+30 BIT E/A),
DIA in E-PA
75x-507 2DA(+12 BIT A),
DIA in E-PA