The consistent user data transfer per process image is supported by the following
S7 CPUs:
from the CPU 318 and S7-400 CPUs as of firmware version V3.0.0
from all S7-300 CPUs with MMC
for all other S7-300 and S7-400 CPUs, the mandatory installation of SFCs 14
"DPRD_DAT" and 15 "DPWR_DAT" is required.
The Vision Sensor VS 130 -2 detects the transmission rate on PROFINET
automatically. PROFINET is operated in 100 Mbps full duplex mode.
Follow the procedures below when entering the device name for the
VS 130-2/VS 130-2vcr:
Step
1
2
Note
When installing a CPU 317-2 PN/DP, in the individual network in the Properties
window of the PROFINET I/O system (slot X2) on the "Options" tab, you have to
select "Transmission medium/duplex": "Automatic Settings"
Attention
VS 130-2 does not support an update time less than 4 ms and cannot be set to
lower update times. If you are setting up the configuration with STEP 7 V5.3 +
SP1, the minimum update time for all PROFINET IO devices of the affected
PROFINET system changes to 4 ms.
Vision Sensor SIMATIC VS 130-2/VS 130-2vcr
A5E00475759-01
Activity
In HW Config, open the properties window of the VS 130-2 and enter the device
name there. When you are done, save and compile the hardware configuration.
Inform the VS 130-2 of the device name you just specified. This is done in three
ways:
In HW Config, select PLC > Ethernet > Assign Ethernet Address... and click
the "Browse" button. Following this, all the devices connected to the PNIO
system will be displayed (Caution: VS 130-2 must be in IP mode "PNIO"
otherwise it is not displayed!). Select the VS 130-2 using its MAC address
and identify it, if need be, using the "Blink" button (The "LINK" LED will blink
at the Ethernet connector on the VS 130-2.). Enter the device name and
click on the "Assign Name" button.
Enter the device name directly in the processing unit (Connect > Ports >
PNIO > Devname).
Assign and transfer the device name using the applet (Connections
Part 1/3: Ports, PROFINET IO, Device name parameter).
Process Interface
6-5