Operator Input
The text display in the Adjustment status of the Vision Sensor has the following
meaning:
"Adjust: live": No code could be decoded yet (corresponds to "Recognition:
running" on the setup support).
"Adjust: read": No currently read code could be decoded (corresponds to
"Recognition: successfully finished" on the setup support).
If an error occurs, an error number is output here. You will find the meaning in
the following table.
No. Description
0
The connected sensor type is
not supported.
1
No sensor connected.
2
DISA changed at an invalid time
(during training)
3
During training, the correct
sequence of applied signals is
not kept to.
4
The code could not be recreated. Run the training again.
5
The send buffer is full because
the data cannot be sent in an
adequately short time,
6
The send buffer is full because
the data cannot be sent in an
adequately short time or the
server does not confirm receipt
of the data in good time
7
The transfer of the last read
result is not yet completed, the
next read result is, however,
already available, or the DP
master or IO controller does not
reply within the handshake
monitoring time (parameter
Connect >Ports >DP >Timeout
on processing unit or within the
time limit parameter in
PROFIBUS DP in Part 1/3: Ports
of the Connections dialog in the
setup support, parameter
Connect >Ports >PNIO
>Timeout on processing unit or
within the time limit parameter in
PROFINET IO in Part 1/3: Ports
in the "Connections" dialog in the
setup support).
8
The DP settings are not correct
9
No code was found in the image
during training.
5-52
Possible Remedies
Connect a sensor supported by
VS 130-2/VS 130-2vcr.
Connect the sensor to the processing unit
correctly.
Check the sequence of applied signals. Start the
training again.
Check the sequence of applied signals. Start the
training again.
Reduce the trigger frequency or process the
results more quickly on the server. A high load on
the network to which the processing unit is
connected can also block the transfer of the data.
If necessary, check the network connection.
Reduce the trigger frequency or reduce the
amount of diagnostic data to be archived. Process
the results on the server faster. A high load on the
network to which the processing unit is connected
can also block the transfer of the data. If
necessary, check the network connection.
Reduce the trigger frequency or process the
results more quickly.
If necessary, change the transmission rate for the
DP configuration or the update time for the
PROFINET configuration.
Correct the DP settings.
Position the code within the image or improve the
image quality.
Vision Sensor SIMATIC VS 130-2/VS 130-2vcr
A5E00475759-01

Advertisement