Siemens SIMATIC Vision Sensor VS 130-2 Manual page 137

Hide thumbs Also See for SIMATIC Vision Sensor VS 130-2:
Table of Contents

Advertisement

No.
Signal
Bit-No. as of
Diagnostic
byte 0 (DP)
17
Lamp overload 15
18
Reserved
16
code number
19
PROFINET
-
I/O Error
20
Internal File
5
Error
Vision Sensor SIMATIC VS 130-2/VS 130-2vcr
A5E00475759-01
Value
Description
(PROFINET)
W#16#500F
The IR lighting unit is
overloaded.
Below you will see the
maximum trigger frequency fT
for the selected shutter speeds
TB:
TB = 500 µs: fT = 60 Hz
TB = 1000 µs: fT = 40 Hz
TB = 2000 µs: fT = 20 Hz
TB = 3000 µs: fT = 13 Hz
TB = 4000 µs: fT = 10 Hz
TB = 5000 µs: fT = 8 Hz
TB = 6000 µs: fT = 7 Hz
TB = 7000 µs: fT = 6 Hz
TB = 8000 µs: fT = 5 Hz
TB = 9000 µs: fT = 4.5 Hz
TB = 10000 µs: fT = 4 Hz
Note: Trigger frequencies >
33 Hz are not practicable.
W#16# 5010
You are attempting to train
code number 15 over digital
I/O or PROFIBUS DP or
PROFINET IO. This is,
however, are reserved for
automatic learning.
W#16# 5011
An error occurred in
PROFINET I/O communication
W#16# 5005
An error occurred when saving
to the read-only memory.
Diagnostics
Possible
Remedies
Reduce the trigger
frequency or
reduce the shutter
speed.
Select a code
number between
1 and 14.
Make sure that the
parameters for
communication
over
PROFINET I/O
and the
communication
partners are
correctly
configured and
active. Check the
connection to the
I/O controller.
Contact Customer
Support if this error
occurs often.
7-5