Note
The consistent user data transfer per process image is supported by the following
S7 CPUs:
from the CPU 318 and S7-400 CPUs as of firmware version V3.0.0
•
from all S7-300 CPUs with MMC
•
for all other S7-300 and S7-400 CPUs, the mandatory installation of SFCs 14
"DPRD_DAT" and 15 "DPWR_DAT" is required.
The Vision Sensor VS 130 -2 detects the transmission rate on PROFIBUS
automatically. Even if the transmission rate has changed, this is detected
automatically. The following values possible:
•
9.6 Kbps
•
19.2 Kbps
•
45.45 Kbps
•
93.75 Kbps
•
187.5 Kbps
•
500 Kbps
•
1.5 Mbps
•
3 Mbps
•
6 Mbps
•
12 Mbps
The PROFIBUS address of the VS 130-2 is set in the Settings > Ports > DP Addr.
menu of the processing unit. Possible values are 1, ... 125.
Changing the PROFIBUS address via PROFIBUS is not supported.
If you assign parameter values to the Vision Sensor VS 130-2 via PROFIBUS, you
can only set its default values (all zero). If you enter values other than zero here, a
slave diagnostic message is generated ("Invalid DP parameters"). If you use an S7
CPU as the DP master, a diagnostic interrupt is triggered (no OB82 start because
the CPU is in STOP): "Faulty module" is entered in the diagnostic buffer and the
"SF" LED lights up.
If you encounter problems when integrating in HW Config, you will find information
on possible causes in Product description and Important Requirements for
Installation.
Vision Sensor SIMATIC VS 130-2/VS 130-2vcr
A5E00475759-01
Process Interface
6-3