External Sensor Types - Fourier DataNet User Manual

Wireless intelligent logging network
Table of Contents

Advertisement

3.7.2.
DNL910, DNL920 and PA Models
Each of the four input channels of these data logger models
are multi-purpose and can be individually configured to any of
the following types and ranges.
Sensor
Current
Contact
Frequency
Pulse Counter
Temperature
PT100 (2-wire)
Temperature TC-J
Temperature TC-K
Temperature TC-T
Voltage
Voltage

External Sensor Types

Measurement
Range
4 to 20 mA
Open (0) /
Close (1)
20 Hz to 4 KHz
1 to 65,536 pulses
0 to 4 KHz
-200 to 400 ºC
-200 ºC to 1,000 ºC
-200 ºC to 1,000 ºC
-200 ºC to 400 ºC
0 to 1 V
0 to 50 mV
49
Accuracy
± 0.5 %
N/A
N/A
N/A
-200 to -60 ºC ±0.5 %
60 to 400 ºC ±0.5 %
-60 to 60 ºC ±0.3 ˚C
-200 to -60 ºC ±0.5 %
60 to 1,000 ºC ±0.5 %
-60 to 60 ºC ±0.5 ˚C
-200 to -60 ºC ±0.5 %
60 to 1,000 ºC ±0.5 %
-60 to 60 ºC ±0.5 ˚C
-200 to -60 ºC ±0.5 %
60 to 400 ºC ±0.5 %
-60 to 60 ºC ±0.5 ˚C
± 0.5 %
± 0.5 %
Available
Inputs
In-1 to In-4
In-1 to In-4
In-4 only
In-4 only
In-1 to In-4
In-1 to In-4
In-1 to In-4
In-1 to In-4
In-1 to In-4
In-1 to In-4