9.13 PID parameters

PID control is used for process control mode normal. For the aim of that the object which be controlled is stabilized as
the PID given, it adjusts inverter output frequency to form passive feedback PID adjustment by series of proportional,
integral, differential calculation by difference between the feedback of that be controlled and the inverter PID given.
Fb.00
PID give signal source
Use to set the input channel of PID controller given signal.
0: Keyboard number given PID Decided by [Fb.01] setting.
1: Keyboard potentiometer
2: Terminal VS1 voltage analog
3: Terminal VS2 voltage analog
4: Terminal AS current analog
5: Terminal PUL pulse signal
input terminal on
output terminal on
Setting range: 0-8