AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
[F2.33]/[F2.35] delay frequency. While output arrives or lower than [F2.32]/[F2.34] setting, FDT 1/2 terminal stops
output signal after [F2.33]/[F2.35] delay frequency.
Speed arriving checkout
F2.36
range
While output frequency arrive or approach give frequency, output terminal Y1/Y2/TA-TB-TC output valid signal if it is
selected as "give frequency arriving". This function can used to adjust test range offset.
give frequency
output frequency
frequency arrive
output signal
F2.37
Over load pre alarm level
F2.38
Over load pre alarm delay
While output current is over [F2.37] setting continuously, the output terminal outputs valid signal after [F2.38] delay
frequency. While output current is lower than [F2.37] setting, the output terminal outputs invalid signal after [F2.38]
delay frequency.
F2.39
Under load pre alarm level
F2.40
Under load pre alarm delay
While output current is equal to or lower than [F2.39] setting, the output terminal outputs valid signal after [F2.40] delay
frequency. While output current is higher than [F2.39] setting, the output terminal outputs invalid signal after [F2.40]
delay frequency. 100.00% corresponding to motor rated current.
Setting range: 0.00- Max frequency
ON
frequency arrive test show
Setting range: 0.0-200.0%
Setting range: 0.0-100.0s
Setting range: 0.0-200.0%
Setting range: 0.0-100.0s
95
Function Parameter specifications
output frequency
ON
Factory set: 0.00Hz
frequency arrive
checkout range(F2.36)
time
Factory set: 180.0%
Factory set: 0.5s
Factory set: 30.0%
Factory set: 0.5s