Veichi AC90 Manual page 144

Tension control frequency inverter
Table of Contents

Advertisement

AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
multi steps terminal 4(X6)
multi steps terminal 3(X5)
multi steps terminal 2(X4)
multi steps terminal 1(X3)
FC.15
PLC run mode selections
LED "0" digit: cycle mode
0: Stop after single cycle While receiving order, inverter run from the first step, time unit is set by [FC.15] LED "00"
digit. Running time is set by [FC.16-FC.30] . Running direction and ACC/DEC time is selected by [FC.31-FC.45] . Turn to
next step while run time is over, run time, direction, ACC/DEC time of every step can be set separately. Inverter output 0
Hz while finished 15 steps running. If one step running time is 0, it will skip this step.
1: Continuous cycles Inverter not stop and runs at the latest speed while finished 15 steps running. Time unit is set by
[FC.15] LED "00" digit. Run time is set by [FC.16-FC.30] . Run direction and ACC/DEC time is selected by
[FC.31-FC.45] .
2: Keep final value after single cycle Inverter back to 1
[FC.15] LED "00" digit. Run time is set by [FC.16-FC.30] . Run direction and ACC/DEC time is selected by
[FC.31-FC.45]
frequency
5X
4X
3X
2X
1X
ON
ON
ON
ON
REV(X3)
FWD(X3)
Setting range: 0000-2212
6X
7X
8X
9X
10X
11X
12X
ON
ON
ON
ON
ON
ON
ON
ON
MULTI STEP TIME ORDER
step while finished 15 steps running. Time unit is set by
st
139
Function Parameter specifications
time
13X
14X
15X
ON
ON
ON
ON
ON
Factory set: 0000