AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
X7
X8
PLC
Pulse input
PUL
A01
Analog output
A02
AS
Analog input
VS1
VS2
+10V
Signal auxiliary
power supply
GND
A+
Communication
terminal
B-
Chart 3-10:AC90 series inverter control loop terminals array and definition
Control loop terminal wiring specification
●
Terminal
A+ B-
+10V GND A01 A02
VS1 VS2 AS
+24V COM Y1 Y2 TA
TB TC PLC PUL X1 X2
X3 X4 X5 X6 X7 X8
Multi-function contact
input 7(exterior fault
input)
Multi-function contact
input8(torque/speed
control switch)
Multi-function
contact input common
terminal
Pulse input
Analog output 1
Analog output 2
Current analog input
Voltage analog input 1
Voltage analog input 2
Signal auxiliary power
supply terminal
Signal auxiliary power
supply terminal
Communication terminal
A+
Communication terminal
B-
Bolt specification
Fixed moment
(mm)
M2.5
0.4~0.6
M2.5
0.4~0.6
M2.5
0.4~0.6
Chart 3-11:Control loop terminal wiring specification
BASIC OPERATION AND TRIAL RUN
Pulse range:0.0~50.00kHz
Can set the action and object by programme. Physical
type of output signal: 0~10VDC.
Can set the action-object by programme. Physical type
of output signal:0~10V 0~20mA 4~0mA
frequency pulse output, selectable by parameter
[F3.26] or switch J1 J2 J3 (Details in chart 3-5)
As inverter control signal or feedback signal, can set
the act range and response speed by programme?
VS1/VS2 resistance:89KΩ;
AS resistance: 250Ω.
Max output 10VDC/50mA
Common auxiliary power of analog output, analog input
signal.
RS485 communication port
Cable specification
(N·m)
(mm
2
0.75
0.75
0.75
27
Cable type
)
Twisted-pair shielded
cable
Twisted-pair shielded
cable
Shielded cable