Chapter 5 Fault Diagnoses and Processing

This chapter explains the display contant and process of the inverter fault, alarm and operation fault. It also simply
explains the bad situation caused by inverter or motor fault and how to solve it. For the adjustment guide in trial run,
please refer to this chapter too.

5.1 Fault types

Type
While inverter detect fault, the state likes this:
Equipment fault
External fault

5.2 Fault information and details

Keyboard
Fault
display
code
L.U.1
E.LU2
E.oU1
E.oU2
Keyboard display character showing fault content.
Inverter stops output. Motor free slide stops.
While function F2.22/F2.23 is set as 3(output fault), Y1/Y2 terminals output valid
open-collector digital output.
While function F2.24 is 3(fault output), TA-TC terminals output open passive digital
output.
While there is fault as OL, OC, SC, OV, UL2, if FA.15 is not 0, the inverter will restart
automatically after FA.16 setting time.
In certain application occasions, external related equipments fault signals are considered
in the inverter control system as usage of monitoring, protection or switch control. At this
time, if one multi function terminal is defied as "external fault", the inverter stops output
alarm signal.
Fault type
Power supply is too low
Too low while
Voltage detection circuit is
stop
abnormal
Power supply is too low
Power capacitance is too
small, or there is big
Too low
impact current in the
voltage in run
power grid.
Inner DC main contactor is
not closed.
Power voltage fluctuation
Acc
over limit.
over-voltage
Start running motor .
Deceleration time is too
short.
Dec
Load potential energy or
over-voltage
inertia is too large.
Power voltage fluctuation
over limit.
BASIC OPERATION AND TRIAL RUN
Inverter action while fault happens
Possible causes
50
Treatment
Check input power, eliminate
fault.
Seek support from factory.
Check input input power,
eliminate fault.
Improve power-supply system.
Seek support from factory.
Detect power voltage and
eliminate fault.
Restart motor until it totally
stop.Set F1.00 as 1or 2.
Prolong deceleration time
properly.
Reduce load inertia or improve
inverter capacitance or add
braking unit.
Detect input power and clear
fault.