Terminal running protection
F1.31
selection
LED "0" digit: while electrify
0: Terminal running order invalid while electrify Terminal controls stop firstly, then start.
1: Terminal running order valid while electrify Terminal controls start directly.
LED "00" digit: while switch the run order give channel
0: invalid Terminal controls stop firstly, then start.
1: valid Terminal controls start directly.
JOG running frequency
F1.32
setting
F1.33
JOG ACC time
F1.34
JOG DEC time
JOG running frequency setting: Set output frequency while JOG.
JOG ACC time: When [F1.13] LED"0"digit is 0, it means the time need for output frequency ACC from 0.00Hz to max
frequency [F0.09]. When [F1.13] LED"0"digit is 1, it means the time need for output frequency ACC from 0.00Hz to
50.00Hz. Details see [F1.13].
JOG DEC time: When [F1.13] LED "0"digit is 0, it means the time need for output frequency DEC from max frequency
[F0.09] to 0.00Hz. When [F1.13] LED "0"digit is 1, it means the time need for output frequency DEC from 50.00Hz to
0.00Hz.
Note: JOG run frequency set is only limited by [F0.09]. While JOG frequency setting is bigger then [F0.11]
upper limitation, actual JOG output frequency is limited by upper limitation. Only terminal JOG priority is
not limited by run orger channels. Other JOG orders have priority only while the channel is tha same as
others. Such as keyboard JOG is only valid under keyboard control.
F1.35
Jump frequency
F1.36
Jump frequency range
Jump frequency: While running, the frequency avoid running.
Jump frequency range: The up/down frequency range of [F1.35] avoid running.
It can be used for output frequency to avoid machine load resonance point.
Note: Output frequency will through jump frequency area while ACC/DEC.
Setting range :0000-0011
Setting range: 0.00-Max frequency
Setting range: 0.00-650.00s
Setting range: 0.00-650.00s
Setting range: 0.00-Max frequency
Setting range: 0.00-Max frequency
85
Function Parameter specifications
Factory set: 0011
Factory set: 5.00Hz
Factory set: 10.00s
Factory set: 10.00s
Factory set: 0.00Hz
Factory set: 0.00Hz