AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Current roll
12
diameter
13
VS2 input
14
Time per roll
15
Reserved
16
VS1 input
17
VS2 input
18
AS input
19
PUL input
F3.24
A01 output gain
F3.25
A01 output signal bias
A01 output gain: It is used for adjust AO1 terminal output analog.
A01 output signal bias: It is used for adjust AO1 terminal 0 point of output signal.
Corresponding to current
max diameter setting of
Corresponding to current
VS2 input
Corresponding to time from
empty to full roll
Corresponding to current
VS1 input
Corresponding to current
VS2 input
Corresponding to current
AS input
Corresponding to current
PUL input
Setting range: 25.0-200.0%
Setting range: -10.0-10.0%
Min output corresponding
to 0 meter
Min output corresponding
to VS2 input lowest limit
Min output corresponding
to 0s
Min output corresponding
to VS1 input lowest limit
Min output corresponding
to VS2 input lowest limit
Min output corresponding
to AS input lowest limit
Min output corresponding
to PUL input lowest limit
98
Function Parameter specifications
Max output corresponding to
max diameter
Max output corresponding to
VS2 input upper limit
Max output corresponding to
time from empty to full roll
Max output corresponding to
VS1 input upper limit
Max output corresponding to
VS2 input upper limit
Max output corresponding to
AS input upper limit
Max output corresponding to
PUL input upper limit
Factory set: 100.0%
Factory set: 0.0%