AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
39: Frequency channel switch terminal 4
It is valid only when [F0.03] is set as 12. Main frequency input channel is selected by terminal. 4 terminals can be
combined to 0-11 which is corresponding to frequency input channels 0-11 of [F0.03]. Details refer to [F0.03].
40: Timer touch terminal Closed is valid.Detail refer to [F2.25-F2.26].
41: Timer clear terminal Closed is valid.Detail refer to [F2.25-F2.26].
42: Counter clock input terminal Detail refer to [F2.27-F2.28].
43: Counter clear terminal Closed is valid.Detail refer to [F2.27-F2.28].
44: DC brake order At stop state, it can start DC brake function.Details refer to [F1.09]. If input run order or JOG order,
DC braking will be stopped.
45: Pre-excitation order terminal At stop state, it can start pre-excitation function. If input run order or JOG order,
pre-excitation order is cancelled.
46: Reserved
47: Start magnetic particle clutch function While it is valid, the inverter will start the magnetic particle clutch function.
Details see[F7.14-F7.17]
48: PID parameter switch terminal 1
49: PID parameter switch terminal 2
50: Initial roll diameter setting terminal 1
diameter only when parameter[F9.14]is set as "0"(terminal selection) in diameter calculation. Details see
[F9.15-F9.17].
51: Initial roll diameter setting terminal 2
diameter only when parameter[F9.14]is set as "0"(terminal selection) in diameter calculation. Details see
[F9.15-F9.17].
52: Linear speed selection terminal
in diameter calculation. This terminal can make the switch between linear speeds setting 1 and linear speed setting 2
coming ture. Details see [F9.28-F9.29].
53:Material thickness selection terminal
thickness) in diameter calculation. This terminal can make the switch between material thickness 1 and material
thickness 2 coming ture. Details see [F9.40-F9.41].
54:Full roll diameter selection terminal
in diameter calculation. This terminal can make the switch between empty roll to full roll time 1 and full roll to empty roll
time 2 coming ture. Details see [F9.44-F9.45].
55: Empty to full roll time selection terminal
in diameter calculation. This terminal can make the switch between empty roll to full roll time 1 and full roll to empty roll
Two different terminals combination corresponds to different initial roll
Two different terminals combination corresponds to different initial roll
It is valid only when parameter [ F9.14] is set as "1"(calculate by linear speed)
It is valid only when parameter[F9.14]is set as "2"(calculate by
It is valid only when parameter[F9.14]is set as "3"(calculate by time)
It is valid only when parameter [F9.14] is set as "3"(calculate by time)
89