AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
1:2-line 2 Run and direction is separate. FWD terminal X1 is run terminal. FWD terminal X2 state decides direction.
K2
K1
0
1
1
0
2:3-line 1 Xi is stop run terminal. Run order is decided by FWD terminal X1. Direction is controlled by REV terminal X2.
Xi is valid input.
K1
direction control
0
1
3:3-line 2 Xi is stop run terminal. Run order is decided by FWD terminal X1or REV terminal X2. Direction is controlled
by both terminals.
Note: SB1: stop button. SB2: FWD button. SB3: REV button. Xi is set as 3 multi function input terminal [ 3 line
control (Xi)].
F2.13
Terminal act mode
Only valid while [F0.02] is 1 and [F2.12] is set as 0 or 1.
LED "0" digit: free stop terminal reset mode
0: Reset to original order while invalid
1: Not reset to original order while invalid
LED "00" digit: emergency stop terminal reset mode
0: Reset to original order while invalid
1: Not reset to original order while invalid
run order
stop
0
0
FWD
1
REV
stop
1
SB1
FWD
REV
2: 3-line 1
X1
SB2
SB1
SB3
X2
Xi
COM
Setting range: 0000-0111
K1
X1
FWD order(run while close)
K2
X2
REV order(run while close)
COM
common input port
1: 2-line 2
frequency inverter
SB2
X1
run order(run while on)
Xi
stop order(stop while off)
K1
X2
FWD/REV order(run while close)
COM
common input port
frequency inverter
FWD order(run while close)
REV order(run while close)
stop order(stop while close)
common input port
3: 3-line 2
91
Function Parameter specifications
frequency inverter
Factory set: 0111