AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Jumping frequency
FC.53
amplitude
Swing frequency ACC
FC.54
time
Swing frequency DEC
FC.55
time
Swing frequency control process: ACC according ACC time to [FC.49] and wait time [FC.50] , run to swing centre
frequency according ACC/DEC time, then run cycle as setting of [FC.51] , [FC.52] , [FC.53] and [FC.54] ,DEC to stop
according ACC/DEC time while receiving stop order.
LED "0" digit: swing frequency control
0: invalid
1: valid
LED "00" digit: swing frequency get in mode
0: automatic Run as frequency [FC.49] for time [FC.50] after start, and entry swing frequency running.
1: manual Run as frequency [FC.49] after start, and entry swing frequency running while multi function input terminal is
valid. Exit and run as frequency [FC.49] while it is invalid.
LED "000" digit: AW control
0: variable AW is variable according the centre frequency.
1: fixed AW is decided by max frequency and [FC.51] .
LED "0000" digit: reserved
Jumping frequency amplitude: Set jumping frequency in swing frequency running.
Swing frequency pre-set: Set frequency before swing frequency running.
Pre-set frequency hold time: While [FC.48] LED "00" digit is 0, it used to set the pre-set frequency holding time befor
swing frequency running. While manual swing frequency get in, it is invalid.
AW: Set frequency swing amplitude while swing frequency control.
Swing frequency ACC time:
Swing frequency DEC time:
Setting range: 0.0-50.0%
Setting range: 0.00-650.00s
Setting range: 0.00-650.00s
Jumping frequency = AW x [FC.51]
Variable AW: AW=centre frequency x [FC.51]
Fixed AW: AW=max frequency [F0.09] X [FC.51]
142
Function Parameter specifications
Factory set: 0.0%
Factory set: 5.00s
Factory set: 5.00s