AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
2: REV
3: Fault trip alarm 1(alarm while fault self-recover)
4: Fault trip alarm 2(no alarm while fault self-recover)
5: Fault retry
6: Out fault stop
7: Under voltage The frequency converter displays "E.LU1/2" for the voltage is excessively low, output signal.
8: Finish ready for running
9: Output frequency level test 1(FDT1)
10: Output frequency level test 2(FDT2) When the output frequency of frequency converter is over test level
[F2.32]/[F2.34] setting, it outputs valid signal after [F2.33]/[F2.35] delay frequency. When output frequency is lower
than test level, it outputs invalid signal after delay frequency. Details see [F2.32-F2.35].
11: Frequency arrive Details see [F2.36].
12: Run as 0 speed
13: Upper frequency limit arrive
14: Lowest frequency limit arrive
15: Program running cycle finished One cycle finished, it output 500ms signal.
16: Program running step finished
17:PID feedback over upper limit While PID feedback arrive [Fb.16] and still over limit after [Fb.14] delay time, it
output valid signal.
18:PID feedback under lowest limit While PID feedback arrive [Fb.17] and still over limit after [Fb.14] delay time, it
output valid signal.
19: PID feedback sensor wire break Details see [Fb.14-Fb.17].
20: Reserved
21: Timer time arrive Details see [F2.25-F2.26].
22: Counter arrive biggest value Details see [F2.27-F2.28].
23: Counter arrive setting Details see [F2.27-F2.28].
24: Energy braking Details see [FA.08].
25: PG feedback break Details see [F5.15-F5.17].
26: Emergency stop
27: Pre alarm output for over load It output valid signal while output current arrive or over [F2.37] and after [F2.38]
delay time.
28: Pre alarm output for under load It output valid signal while output current is smaller or equal to [F2.39] and after
[F2.40] delay time.
29: Roll diameter arrive output
valid signal if the current diameter is bigger or equal to the max diamerter[F9.12]
Note: Relay output terminal TA-TC on and TB-TC off is valid signal. Y1, Y2 output terminal with low level is
combined to (+24V) terminal to output valid signal 24V power.
Output frequency level
F2.32
1(FDT1)
F2.33
FDT1 lag
Output frequency level
F2.34
2(FDT2)
F2.35
FDT2 lag
Used to set test level. While output arrives or higher than [F2.32]/[F2.34] setting, FDT 1/2 terminal outputs signal after
While inverter calculates roll diameter under tension control mode, it outputs
Setting range: 0.00- Max frequency
Setting range: 0.00- Max frequency
Setting range: 0.00- Max frequency
Setting range: 0.00- Max frequency
94
Function Parameter specifications
Factory set: 30.00Hz
Factory set: 0.00Hz
Factory set: 50.00Hz
Factory set: 0.00Hz