Veichi AC90 Manual page 89

Tension control frequency inverter
Table of Contents

Advertisement

AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
If [FA.01] "000" and "0000" digit is 1 emergency stop, the inverter wills DEC to stop according this time and alarm fault.
Details refer to [FA.01].
While multifunction terminal is set as emergency stop, refer to detail [F2.29-F2.31].
F1.25
FWD&REV dead area
F1.26
Min output frequency
FWD&REV dead area: Waitting time at 0.0Hz while switch between FWD/REV. It sets for equipment with machine
dead area while big inertia load and change direction.
Min output frequency: If lower than this frequency, inverter output 0.00Hz.
F1.27
0 speed hold torque
Set output torque at 0 speeds.
F1.28
0 speed torque keep time
It sets the torque keep time while running at 0 speed.Begin time while run frequency is 0Hz. Inverter stop output while 0
speed torque keep time arrives.
Right set this time can save energy effectively while protect motor
Power off restart action
F1.29
selection
Power off restart waiting
F1.30
time
Power off restart action selection
0: invalid Only run with order power on again.While keyboard control, RS485 communication control or optional card
control, automatic clear running order while power off.
While exterior terminal control, run as [F1.31] setting.
1: Valid If inverter is at run state before power off, it start automatically after [F1.30] waiting time. While waiting, it does
not accept any orders. But if stop order, it will not restart.
Note: It can make machine automatic re-start while power recovers. Please use it carefully.
Power off restart waiting time: While [F1.29] is valid, inverter restarts after [F1.30] waiting time.
Setting range: 0.0-120.0s
Setting range: 0.00-60.00Hz
Setting range: 0.0-150.0%
Setting range: 0.0-500.0s
Setting range: 0-1
Setting range: 0.00-650.00s
84
Function Parameter specifications
Factory set: 0.0s
Factory set: 0.50Hz
Factory set: Accord model
Factory set:5.0s
Factory set: 0
Factory set: 0.50s

Advertisement