AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Must meet:0≤F1≤F2≤F3≤F4≤F5≤max frequency;0≤V1≤V2≤V3≤V4≤V5≤100.0%
V1、V2、V3、V4、V5 is based on motor rated voltage.
Output voltage
F8.11
percentage
Output voltage adjustment coefficient adjusts output voltage of inverter to meet different V/F requirement.
F8.12
Torque improve
Torque improve close
F8.13
frequency
Torque improve: Improve low frequency torque trait by voltage compensation. Please set it rightly. If too high, motor
maybe happens over excitation at low frequency running, over heat while long time, even over current protection or can
not start normally.
Note: while [F8.00] is 1, [F8.12] is invalid.
Torque improve close frequency: Set torque improve valid range. While output frequency is over this value, torque
improving function stops. 100% is corresponding to motor rated frequency.
Setting range: 25-100%
Setting range: 0.1-30.0%
Setting range: 0.0-100.0%
115
Function Parameter specifications
Factory set: 100%
Factory set: Accord model
Factory set: 20.0%