1: valid to terminal order While terminal given signal, STOP key can control to stop.
LED"00"digit: communication control
0: invalid to communication order While terminal given signal, STOP key can not control to stop.
1: valid to communication order While terminal given signal, STOP key can control to stop.
LED "000" digit: reserved
LED "0000" digit: reserved
Note: While valid to terminal order or communication order, inverter is in stop lock state after press STOP key.
If inverter needs to restart, stop oder needs to be given by selected order channel to unlock stop state firstly.
UP/DOWN key modification
F4.04
selections
LED "0" digit: keyboard UN/DOWN key modify selection
0: Invalid UP/DOWN key can not modify parameters.
1: Modify frequency setting by key board numbers (F0.08) UP/DOWN key can modify parameters [F0.08].
2: Reserved
3: Modify PID give setting by key board numbers (Fb.01) UP/DOWN key can modify parameters [Fb.01].
4: Reserved
LED "00" digit: keyboard UN/DOWN key store selection
0: No save after power down
1: Save after power down
It is used to select whether save the parameter modified by UP/DOWN key while power cut.
LED "000" digit: reserved
LED "0000" digit: reserved
F4.05
Function parameter copy
0: No operation
1: Send machine parameters to keyboard and save
2: Send parameters saved by keyboard to machine
F4.06
Keyboard potentiometer lowest
F4.07
limit
Keyboard potentiometer lowest
F4.08
limit corresponding setting
Keyboard potentiometer upper
F4.09
limit
Keyboard potentiometer upper
F4.10
limit corresponding setting
Keyboard potentiometer lowest limit: It defines the lower limit of the signal gived by potenmeter. Inverter treat the
voltage lower than this value as the lower limit signal.
Keyboard potentiometer lowest limit corresponding setting: It sets ratio of keyboard potentiometer lower limit.
Keyboard potentiometer upper limit: It defines the upper limit of the signal gived by potenmeter.Inverter treat the
voltage higher than this value as the lower limit signal.
Setting range: 0000-0014
Setting range: 0-2
Reserved
Setting range: 0.00-5.00V
Setting range: 0.00-100.00%
Setting range: 0.00-5.00V
Setting range: 0.00-100.00%
101
Function Parameter specifications
Factory set: 0011
Factory set: 0
Factory set: 0.50V
Factory set: 0.00%
Factory set: 4.50V
Factory set: 100.00%