AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
frequency, free stop frequency, stop DC brake start frequency, jump frequency and so on. Max
frequency, upper limitation and lowest limitation relationship as below:
F0.14
ACC time 1
F0.15
DEC time 1
ACC time 1: When [F1.13] LED "0"digit is 0, it means the time needed for output frequency accelerate from 0.00Hz to
max frequency [F0.09]. When [F1.13] LED "0"digit is 1, it means the time needed for output frequency accelerate from
0.00Hz to 50.00Hz. Details refer to [F1.13].
DEC time 1: When [F1.13] LED "0"digit is 0, it means the time needed for output frequency decelerate from max
frequency [F0.09] to 0.00Hz. When [F1.13] LED "0"digit is 1, it means the time needed for output frequency decelerate
from 50Hz to 0.00Hz. Details refer to [F1.13].
This frequency inverter can set 4 kinds of ACC/DEC time max. If need to select other ACC/DEC time group, it must to
select by control terminal. Details refer to [F2.00-F2.07] and [F1.18-F1.23].
ACC time is only valid for normal speed up process, not including start per-excite, start DC brake time and start
frequency hold time. DEC time is only valid for normal speed doen process, not including stop DC brake time.
During process running, ACC/DEC time 1 is defined as first kind of ACC/DEC time. The other 3 kinds of ACC/DEC time
details refer to [F1.18-F1.23] please.
JOG ACC/DEC time set by [F1.33, F1.34] alone.
Setting range: 0.01-650.00s
Setting range: 0.01-650.00s
78
Function Parameter specifications
Factory set: Accord model
Factory set: Accord model