4.14 Remote Station Applications

4.14.1

Keltron Model 3158 Installation

The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The
3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete
information.
1.
Wire the 3158 to the control panel as shown in the connection list and Figure 4-42.
2.
Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3.
Program control panel Relay 1 for alarm.
4.
Program Flexput circuit 5 for alarm.
5.
Program Flexput circuit 6 for supervisory non latching.
Terminal #
3158 Term. 1
To Keltron receiving equipment
3158 Term. 2
To Keltron receiving equipment
3158 Term. 3
Earth ground
3158 Term. 4
Not used; no connection.
3158 Term. 5
Control panel SBUS OUT +
3158 Term. 6
Control panel SBUS OUT –
3158 Term. 7
Control panel I/O5 O
Not suitable for remote station
protected premise service
where separate transmission
circuits are required for fire
supervisory (if applicable), and
trouble signals.
Intended for connection to a
polarity reversal circuit of a
remote station receiving unit
having compatible ratings.
Table 4-5: Keltron 3158 to Control Panel Connections
Connects To
Figure 4-42 Keltron 3158 Connection to Control Panel
Terminal #
3158 Term. 8
3158 Term. 9
3158 Term. 10
Control panel I/O5 X
Control panel Relay 1 COM
Control panel Relay 1 NO
Example
4-33
151430-L8
Connects To
Control panel Relay 1 COM
Control panel I/O6 O
Control panel I/O6 X
Control panel Relay 1 NO
Control panel Trouble COM