A.2. INFO A6 mode as a trigger of external signals
If the machine is connected to an individual dosing system using pumps controlled directly from the A6 board,
the Info A6 mode can be used to trigger the signals corresponding to these pumps to dose the desired product at
the right time.
A.2.1. Example of using multiple external dosings of the same duration
A washing process which requires dosing six different products in the same phase, two of them via the
machine's internal dosing and the remaining four using four pumps outside the washing machine, connected to
Outputs d6, d8, d11 and d12 of the A6(I/O2) board.
The first internal dose should last 5 seconds, the second for 15 seconds and the remaining four for 10 seconds.
The following table shows how to enter this information when setting a program:
Pr
2
Ph
1
2
3
60
2
1
5
0
3
1
5
0
4
2
4
0
Phase
Symbol
Value
1
5
2
Ph1
15
202
10
Appendices to the manual
140
1
5
2
32
0
0
0
32
0
0
0
32
4
8
0
Description
Selection of first dosing, powder product compartment.
Duration of the first dosing. In this case, 5 seconds.
Selection of second dosing, powder product compartment.
Duration of the second dosing. In this case, 15 seconds.
Selection of the A6(I/O2) board signals that must be activated. If the table in
Section 7.4.3 is consulted, it will show that 202 corresponds to Outputs d6, d8, d11
and d12.
Dosing time: 10 seconds. As Outputs d6, d8, d11 and d12 are activated in the same
phase, all four will have the same duration.
15
202
10
5
0
0
0
5
0
0
0
5
0
0
0
5
48 min
6
0
0
2
2
0
1
1
2
0
1
1
3
0
1
6