Pid Upper Limit; Pid Lower Limit; Pid Scaling; Pid Destination - Emerson unidrive sp User Manual

Universal variable speed ac drive for induction and servo motors
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Parameter
Keypad and
Menu 14
structure
display
14.13

PID upper limit

Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Open-loop, Closed-loop vector, Servo,
Default
Regen
Update rate
Background read
14.14

PID lower limit

Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Open-loop, Closed-loop vector, Servo,
Default
Regen
Update rate
Background read
If Pr 14.18 = 0, the upper limit (Pr 14.13) defines the maximum positive output for the PID controller and the lower limit (Pr 14.14) defines the
minimum positive or maximum negative output. If Pr 14.18 = 1, the upper limit defines the maximum positive or negative magnitude for the PID
controller output. When any of the limits are active the integrator is held.
14.15

PID scaling

Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Open-loop, Closed-loop vector, Servo,
Default
Regen
Update rate
4ms read
14.16

PID destination

Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Open-loop, Closed-loop vector, Servo,
Default
Regen
Update rate
Read on reset
The value written to the destination parameter is (PID controller output x scaling) + PID main reference.
14.17
PID hold integrator
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
Coding
1
Open-loop, Closed-loop vector, Servo,
Default
Regen
Update rate
4ms read
When this parameter is set to 0 the integrator operates normally. Setting this parameter to 1 will cause the integrator value to be held. Setting this
parameter does not prevent the integrator from being reset to zero if the PID controller is disabled.
250
Parameter
Parameter
x.00
description format
FI
DE
Txt VM DP
ND
2
0.00 to 100.00 %
100.00
FI
DE
Txt VM DP
ND
2
±100.00 %
-100.00
FI
DE
Txt VM DP
ND
3
0.000 to 4.000
1.000
FI
DE
Txt VM DP
ND
1
2
Pr 0.00 to Pr 21.51
Pr 0.00
FI
DE
Txt VM DP
ND
0
www.controltechniques.com
Advanced parameter
Macros
descriptions
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
1
RA NC NV
PT
US RW BU
1
1
Serial comms
Electronic
Performance RFC mode
protocol
nameplate
PS
1
PS
PS
1
PS
1
PS
Unidrive SP Advanced User Guide