Setting Load Shed; Setting Temperature And Rh % Offsets; Setting The Sensor Fail Output - Emerson PMAC II Solo Installation And Operation Manual

Pulse modulating and anti-sweat control
Table of Contents

Advertisement

15. Press the
MAX PULSE % and press the
select. Use the
maximum pulse rate generated at the maxi-
mum dewpoint setpoint. Press the
to save changes and go back to the Configu-
ration screen.
MAX PULSE SETPOINT
Figure 1-20 - Maximum Pulse Setpoint Screen

1.5.4.4. Setting Load Shed

16. From the Configuration screen, press the
button to scroll down the list to 6. SET
LOAD SHED and press the
lect. Use the
load shed pulse rate generated when the load
shed input is closed. Press the
save changes and go back to the Configura-
tion screen.
LOAD SHED PERCENTAGE
10%
Figure 1-21 - Load Shed Percentage Screen

1.5.4.5. Setting Temperature and RH % Offsets

17. To adjust the setpoints for temperature and
RH % offsets, press the
down the list to 7. SET TEMP OFFSET and
press the
and
buttons to add or subtract an offset
from the humidity sensor reading. Press the
button to save and go back to the Config-
uration screen.
Programming the UC12PG-R Controller on the PMAC II Solo Panel
button to scroll down to 5. SET
button to
and
buttons to set the
button
100%
button to se-
and
buttons to set the
button to
button to scroll
button to select. Use the
SPACE TEMP OFFSET
Figure 1-22 - Space Temp Offset Screen
18. From the Configuration screen, press the
button to scroll down the list to 8. SET RH%
OFFSET and press the
Use the
and
tract an offset from the humidity sensor read-
ing. Press the
to the Configuration screen.
RH SENSOR OFFSET
12% RH
Figure 1-23 - RH Sensor Offset Screen

1.5.4.6. Setting the Sensor Fail Output

Setting the Sensor Fail Output is the last step for enter-
ing/changing setpoints.
19. From the Configuration screen, press the
button to scroll down the list to 9. SENSOR
FAIL OUTPUT and press the
select. Use the
percentage. This setting determines the
PMAC II Solo output in the event that the RH
or temp sensors are not present or have failed.
Press the
the first Setpoints Configuration screen (Fig-
ure 1-13).
%ON = SENSOR FAILURE
96%
Figure 1-24 - Sensor Failure Percentage Screen
10F
button to select.
buttons to add or sub-
button to save and go back
button to
and
buttons to adjust
button to save and go back to
Overview • 7