Logical Signal Status Report Binstatrep; Identification; Application; Setting Guidelines - ABB RELION 650 Series Applications Manual

Line differential protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 505 363-UEN A
Minimize the number of recordings:
Binary signals: Use only relevant signals to start the recording that is, protection trip,
carrier receive and/or start signals.
Analog signals: The level triggering should be used with great care, since unfortunate
settings will cause enormously number of recordings. If nevertheless analog input
triggering is used, chose settings by a sufficient margin from normal operation values.
Phase voltages are not recommended for trigging.
Remember that values of parameters set elsewhere are linked to the information on a report.
Such parameters are, for example, station and object identifiers, CT and VT ratios.
15.7

Logical signal status report BINSTATREP

15.7.1

Identification

Function description
Logical signal status report
15.7.2

Application

The Logical signal status report (BINSTATREP) function makes it possible to poll signals from
various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs and can be
read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 146: BINSTATREP logical diagram
15.7.3

Setting guidelines

The pulse time
output can be set or reset individually, but the pulse time will be the same for all outputs in the
entire BINSTATREP function.
Application manual
IEC 61850
identification
BINSTATREP
t
t is the only setting for the Logical signal status report (BINSTATREP). Each
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
GUID-F9D225B1-68F7-4D15-AA89-C9211B450D19 v3
t
IEC09000732-1-en.vsd
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
Section 15
Monitoring
303