Logical Signal Status Report Binstatrep; Identification; Application - ABB RES670 Applications Manual

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 407-UEN C
16.7
16.7.1
16.7.2
Phasor measurement unit RES670 2.2 IEC
Application manual
margin from normal operation values. Phase voltages are not recommended for
trigging.
There is a risk of flash wear out if the disturbance report triggers
too often.
Remember that values of parameters set elsewhere are linked to the information on
a report. Such parameters are, for example, station and object identifiers, CT and
VT ratios.

Logical signal status report BINSTATREP

Identification

Function description
Logical signal status report

Application

The Logical signal status report (BINSTATREP) function makes it possible to poll
signals from various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs
and can be read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 92:
BINSTATREP logical diagram
IEC 61850
IEC 60617
identification
identification
BINSTATREP
t
IEC09000732-1-en.vsd
Section 16
Monitoring
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
ANSI/IEEE C37.2
device number
-
-
GUID-F9D225B1-68F7-4D15-AA89-C9211B450D19 v3
t
277