11.2 Protection Interface and Protection Topology

11.2
Protection Interface and Protection Topology
Setting Values
Mode
PPS Synchronization
Blocking of the unbalanced
runtimes
Maximum signal runtime threshold 0.1 ms to 30.0 ms
Maximum runtime difference
Failure indication after
Transm. fail. alarm after
Max. error rate/h
Max. error rate/min
PPS failure indication after
Transmission Rate
Direct connection:
Transmission rate
Connection via communication networks:
Supported network interfaces
Transmission rate
Transmission Times
Priority 1:
Response time, total approx.
For 2 ends
For 3 ends
For 6 ends
Dropout times, total approx.
For 2 ends
For 3 ends
For 6 ends
1104
On
Off
Telegr. and PPS
Telegr. or PPS
PPS synchronization off
Yes
No
0.000 ms to 3.000 ms
0.05 s to 2.00 s
0.0 s to 6.0 s
0.000 % to 100.000 %
0.000 % to 100.000 %
0.5 s to 60.0 s
2048 kbit/s
G703.1 with 64 kbit/s
G703-T1 with 1.455 Mbit/s
G703-E1 with 2.048 Mbit/s
X.21 with 64 kbit/s or 128 kbit/s or 512 kbit/s
Pilot wires with 128 kbit/s
64 kbit/s at G703.1
1.455 Mbit/s at G703-T1
2.048 Mbit/s at G703-E1
512 kbit/s or 128 kbit/s or 64 kbit/s at X.21
128 kbit/s for pilot wires
Minimum
Typical
Minimum
Typical
Minimum
Typical
Typical
Typical
Typical
Increments of 0.1 ms
Increments of 0.001 ms
Increments of 0.01 s
Increments of 0.1 s
Increments of 0.001 %
Increments of 0.001 %
Increments of 0.1 s
8 ms
10 ms
10 ms
14 ms
15 ms
18 ms
20 ms
20 ms
26 ms
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017