Figure 5-3. Distributed Bypass System Can And Pull-Chain Simplified Interface Wiring; Figure 5-4. Distributed Bypass System Ups Can Wiring Without Mobs - Eaton Power Xpert 9395 Installation And Operation Manual

Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order

Figure 5-3. Distributed Bypass System CAN and Pull-Chain Simplified Interface Wiring

Shielded Twisted Pair
UPS 1
CAN Bridge Card J3
NOTE External CAN connections between UPSs require shielded twisted pair wire.

Figure 5-4. Distributed Bypass System UPS CAN Wiring without MOBs

Table 5-2. CAN Bridge Card Wiring Terminations
UPS 1 CAN Bridge Card
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
®
®
Eaton
Power Xpert
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual
CAN
UPS 1
Shielded Twisted Pair
UPS 2
CAN Bridge Card J3
From
UPS 2 CAN Bridge Card
J3–10 (Shield)
UPS 2
Shielded Twisted Pair
UPS 3
CAN Bridge Card J3
(If Installed)
To
UPS 3 CAN Bridge Card
(If Installed)
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
P-164000563—Rev 04 www.eaton.com/powerquality
Installing Options and Accessories
UPS 3
UPS 4
(If Installed)
(If Installed)
CAN Bridge Card J3
(If Installed)
To
UPS 4 CAN Bridge Card
(If Installed)
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
Pull Chain
.
UPS 4
To
J3–8 (L)
J3–9 (H)
5-5