Figure 40. Remote Monitor Panel Ii, Relay Interface Module Ii, Or Supervisory Contact Module Ii Wiring - Eaton Power Xpert 9395 Installation And Operation Manual

Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

Figure 40. Remote Monitor Panel II, Relay Interface Module II, or Supervisory Contact Module II Wiring

UPS Can Card J3
Twisted Pair
Table 32. RMP II, RIM II, or SCM II Wiring Terminations
UPS CAN Card
J3–6 ( TX )
J3–7 (TX)
NOTE
11. To check the operation of the RMP II, ensure that the UPS is supplying the load via inverter or bypass. If
the indicators on the RMP II show the appropriate status, then it is operating correctly.
If the communication link between the UPS and the RMP II is not present, the RMP II performs a self–test
(all indicators flash and the horn beeps at one–second intervals). If the self-test occurs, check all harness
connectors and the fuse for proper seating. If all connections are secure but the RMP II continues to self–
test, replace the fuse with the spare included in the hardware kit. If a fuse replacement does not correct
the problem, contact an Eaton service representative for verification that the RMP II is working correctly.
12. To test the indicator lamps, press and hold the horn silence pushbutton for three seconds. All lamps should
illuminate, and the horn sounds continuously until you release the pushbutton.
RMP II, RIM II, or SCM II
From
RMP II, RIM II, or SCM II
TB1–5 (RDX*)
TB1–4 (RDX)
N/A
TB3 Line
N/A
TB3 Neutral
N/A
Ground Terminal
Setup of the Hot Sync CAN Bridge Card must be performed by an authorized Eaton
Customer Service Engineer. Contact an Eaton service representative to schedule a date.
Eaton
®
Power Xpert
®
To
Tightening Torque
Nm (lb in)
0.9 (8)
0.9 (8)
0.9 (8)
0.9 (8)
2.7 (24) Maximum
9395P-600 Installation and Operation Manual 164000562—Rev 08
Installing Options and Accessories
Ground Terminal
Neutral
120 Vac from
Critical Bus
Line
(Customer
Supplied)
Remarks
Use twisted pair
93