NX_ReadTotalPowerOnTime

The NX_ReadTotalPowerOnTime instruction reads the total power ON time from a Communications
Coupler Unit or NX Unit.
Instruction
Name
NX_Read
Read NX Unit
TotalPower
Total Power ON
OnTime
Time
Variables
Name
Meaning
UnitProxy
Specified Unit
TotalPow-
Total power
erOnTime
ON time
* If you omit an input parameter, the default value is not applied. A building error will occur.
UnitProxy
TotalPow-
erOnTime
Function
The NX_ReadTotalPowerOnTime instruction reads the approximate total power ON time from a Com-
munications Coupler Unit, an NX Unit on the Communications Coupler Unit, or an NX Unit connected to
the NX bus of the CPU Unit.
The accuracy is 1 hour per month.
The Unit from which the total power ON time is read is specified with UnitProxy.
When the value of Done changes to TRUE, the total power ON time has been read.
2-854
FB/FUN
Graphic expression
NX_ReadTotalPowerOnTime_instance
NX_ReadTotalPowerOnTime
Execute
FB
UnitProxy
I/O
Description
Input
Specifies the target NX Unit.
Stores the total power ON time
Output
that was read.
Bit strings
Refer to Function for details on the structure _sNXUNIT_ID.
NX_ReadTotalPowerONTime_instance(
Execute,
UnitProxy,
Done,
Done
Busy,
Busy
Error
Error,
ErrorID
ErrorID,
ErrorIDEx
TotalPowerOnTime
ErrorIDEx,
TotalPowerOnTime);
Valid range
---
Depends on
data type.
Integers
NY-series Instructions Reference Manual (W560)
ST expression
Unit
Default
*
---
0
Times, durations,
dates, and text strings
OK