2 Instruction Descriptions
• Error is TRUE if an error occurred. The meanings of the values of ErrorID and ErrorIDEx are given in
the following table.
Value of ErrorID
16#0419
16#2C00
2-846
Value of ErrorIDEx
16#0000 0000
The data type of UnitProxy is not correct.
16#0000 0401
The specified Unit does not support the instruction.
16#0000 1001
An input parameter, output parameter, or in-out parameter is
16#0000 1002
incorrect.
16#0017 0000
Confirm that the intended parameter is used for the input parame-
16#0020 0000
ter, output parameter, or in-out parameter.
16#0021 0000
The data size of the specified NX object does not agree with the
16#0000 1010
data size specified in WriteDat.
The correct Unit was not specified.
16#0000 1101
Check the Unit.
The size of the read data is too large.
16#0000 110B
Make sure that the read data specification is correct.
16#0000 1110
There is no object that corresponds to the value of Obj.Index.
16#0000 1111
There is no object that corresponds to the value of Obj.Subindex.
16#0000 2101
The specified NX object cannot be written.
The value of WriteDat exceeds the range of the values of the NX
16#0000 2110
object to write.
16#0000 2210
The specified Unit is not in a mode that allows writing data.
Instruction execution was not possible because the specified Unit
16#0000 2213
was performing an I/O check.
Execute the instruction after the I/O check is completed.
The status of the specified Unit does not agree with the value of
the read source or write destination NX object.
Take the following actions if the value of Obj.Index is between
0x6000 and 0x6FFF or between 0x7000 and 0x7FFF.
• Delete the read source or write designation NX object from the
16#0000 2230
I/O allocation settings.
• Reset the error for the specified Unit.
• Place the specified Unit in a mode that does not allow writing
data.
Instruction execution was not possible because the specified Unit
was performing initialization.
16#0000 2231
Wait for the Unit to start normal operation and then execute the
instruction.
Hardware access failed.
16#0000 250F
Execute the instruction again.
16#0000 2601
The specified Unit does not support this instruction.
16#0000 2602
Check the version of the Unit.
16#0010 0000
Execution of the instruction failed.
Execute the instruction again.
16#0000 2603
Make sure that at least one channel is enabled in the selections of
the channels to use.
The NX Unit is not in a status in which it can acknowledge the
16#0000 2621
instruction.
Wait for a while and then execute the instruction again.
The specified Unit does not exist.
16#0001 0000
Make sure that the Unit configuration is correct.
The specified port number does not exist.
16#00110000
Make sure that the Unit configuration is correct.
16#0012 0000
The value of UnitProxy is not correct.
16#0013 0000
Set the variable that indicates the specified EtherCAT Coupler
16#0015 0000
Unit again.
16#0016 0000
Meaning